| Power capacitors | Low-voltage power capacitors rated in kvar, for the system voltage and frequency. Supplied as individual units or capacitor assemblies. | Provide reactive power locally to improve power factor and reduce reactive current drawn from the supply. | Check rated voltage, frequency, kvar, capacitance tolerance, permissible temperature, discharge provisions, and applicable product standards. |
| Capacitor-duty switching devices | Capacitor-duty contactors or other specified switching devices, often one device for each automatically controlled stage. | Connect and disconnect capacitor stages while limiting the effects of capacitor inrush current. | Confirm switching-device ratings, switching frequency, stage arrangement, and suitability for capacitor switching—not just ordinary motor duty. |
| Protection devices | Fuses, circuit breakers, or other overcurrent protection selected for the bank design. | Protect circuits and equipment against specified fault and overcurrent conditions. | Verify voltage, current, breaking capacity, coordination, and whether devices are included for each stage or supplied separately. |
| Power factor controller | Automatic controller with a specified number of switching outputs and configurable target power factor. | Measures the installation’s power factor and switches capacitor stages as reactive-power demand changes. | Check output count, measurement inputs, operating settings, alarms, control supply, and compatibility with the planned stage sizes. |
| Current transformer (CT) | A CT with a specified ratio and accuracy class; it may be included in the kit or supplied by the installer. | Provides the current measurement used by the power factor controller. | Confirm the ratio, installation location, polarity, secondary rating, and compatibility with the controller and electrical system. |
| Detuned reactors (optional) | Series reactors selected with capacitor stages to form a detuned bank where the design requires harmonic mitigation. | Help reduce the risk of resonance between the capacitor bank and the electrical network in harmonic-producing installations. | Require a harmonic assessment. Confirm reactor tuning, current and thermal ratings, capacitor voltage selection, and system compatibility; reactors are not automatically included in every kit. |
| Discharge resistors or devices | Discharge components fitted to capacitors or assemblies, as specified by the design. | Reduce retained voltage after disconnection, subject to the equipment design and applicable requirements. | Confirm discharge performance and required waiting time before access or re-energization from the equipment documentation. |
| Busbars and connection hardware | Busbars, terminals, links, mounting hardware, and specified electrical connectors. | Interconnect capacitor stages and connect the assembly to the panel’s power circuit. | Check current capacity, material, clearances, connection sizes, and whether inter-stage wiring and hardware are part of the CKD scope. |
| Enclosure and mounting parts | Cabinet, backplate, mounting rails, or assembly drawings; enclosure supply depends on the CKD package. | Houses and supports the equipment while providing the specified protection against environmental and access conditions. | Verify dimensions, ventilation, ingress-protection rating, installation environment, clearances, and whether the enclosure is included or locally sourced. |
| Wiring, labels, and documentation | Control wiring, terminal markers, circuit labels, wiring diagrams, assembly instructions, and test information as agreed. | Supports correct assembly, inspection, commissioning, and future maintenance. | Agree on document language, drawing format, wiring scope, test records, and the division of responsibility between supplier and local assembler. |