| Indoor substation or switchgear | Clean, dry, limited UV exposure; controlled access; low risk of salt or industrial contamination. | Focus on system voltage, temporary overvoltage withstand, short-circuit capability, and correct connection clearances. | Standard silicone-rubber housing with the creepage distance required for the actual indoor pollution level. | Confirm coordination with transformer, cable, and switchgear insulation levels; check enclosure ventilation and terminal clearances. |
| Outdoor distribution line | Rain, sunlight, wind, dust, temperature cycling, and possible ice or snow. | Use a weather-resistant polymeric housing, hydrophobic silicone surface, sealed interfaces, and adequate mechanical strength. | Select an outdoor arrester tested for environmental sealing, UV exposure, mechanical loading, and leakage-current stability. | Check line hardware loads, conductor movement, mounting orientation, pollution severity, and local minimum temperatures. |
| Coastal or salt-contaminated area | Salt deposits, high humidity, wind-driven spray, frequent wetting, and elevated surface conductivity. | Increase creepage distance and use a housing with stable hydrophobicity and strong resistance to salt-fog aging. | Use a pollution-specific creepage design rather than selecting only by nominal system voltage; consider periodic washing where applicable. | Classify the site according to the applicable pollution-severity method and review salt-fog, wet-power-frequency, and housing-aging test evidence. |
| Industrial pollution zone | Conductive dust, chemical deposits, combustion by-products, or emissions from industrial processes. | Prioritize contamination performance, creepage distance, hydrophobic recovery, and resistance to chemical attack. | Choose an arrester with pollution-class data and a creepage distance suitable for the measured or assessed contamination level. | Evaluate chemical compatibility, deposit conductivity, cleaning intervals, and the possibility of surface discharge or tracking. |
| High-altitude installation | Reduced air density affects external insulation clearances and may increase cooling constraints. | The arrester electrical characteristics may remain suitable, but external air clearances and insulation coordination require altitude correction. | For sites above approximately 1,000 m, review altitude correction factors specified by the relevant installation standard. | Confirm phase-to-earth and phase-to-phase clearances, creepage requirements, thermal performance, and applicable utility rules. |
| High lightning-density region | Frequent lightning activity, exposed lines, poor shielding, or high ground-flash density. | Consider higher energy capability, short lead connections, low residual voltage, and suitable line-discharge performance. | Use an arrester class and energy rating supported by lightning and network studies, not by voltage rating alone. | Assess line length, tower footing resistance, shielding, backflashover risk, and the number of expected surge events. |
| Transformer terminal installation | Arrester installed close to a transformer bushing, often with short but inductive connecting leads. | Low residual voltage and minimal lead length are important because surge voltage increases with lead inductance. | Mount the arrester as close as practicable to the protected terminal; keep phase and earth leads short and direct. | Verify protection distance, lead routing, grounding impedance, transformer impulse withstand level, and terminal clearances. |
| Motor, generator, or cable-connected equipment | Fast-front transients, cable reflections, switching surges, and possible repetitive operation. | Select suitable discharge characteristics and ensure the arrester does not experience excessive temporary overvoltage or thermal stress. | Install at the equipment terminals or at the cable transition point, with attention to cable length and surge travel time. | Study switching transients, cable configuration, grounding method, motor insulation class, and repetitive surge frequency. |
| Network with frequent temporary overvoltages | Earth faults, load rejection, ferroresonance, resonance, or isolated-neutral operation may produce sustained overvoltage. | The maximum continuous operating voltage (MCOV) must withstand the highest continuous phase-to-earth voltage; short-duration TOV capability must also be checked. | Select MCOV from the actual grounding and fault-clearing conditions, not simply from the nominal line voltage. | Calculate earth-fault factor, fault duration, neutral treatment, system frequency, and arrester thermal recovery capability. |
| Cold, hot, or severe temperature environment | Outdoor temperatures may range from below −40 °C to above 40 °C, depending on the site. | Housing materials, seals, pressure-relief behavior, and thermal stability must match the specified service temperature range. | Specify the complete minimum and maximum operating temperature, including solar heating and enclosure effects. | Review temperature-cycle testing, thermal stability, ice loading, seal performance, and manufacturer-declared service limits. |
| Areas exposed to vandalism or mechanical impact | Public access, vehicle movement, construction activity, or risk of falling objects. | Polymeric housings reduce shattering risk compared with brittle porcelain, but mechanical strength and mounting design remain essential. | Use a mechanically robust arrester with protected mounting, secure terminals, and suitable cantilever or tensile ratings. | Check impact exposure, conductor forces, mounting hardware, enclosure protection, and safe failure or pressure-relief behavior. |
| Typical medium-voltage system example | Three-phase 11 kV network with effectively grounded neutral and outdoor line exposure. | A commonly evaluated starting point is an arrester with approximately 7.65 kV MCOV and 10 kV rated voltage, subject to system studies. | Select the actual MCOV, rated voltage, discharge class, housing creepage, and energy capability for the network configuration. | Confirm grounding, fault duration, insulation coordination, pollution level, lightning exposure, and the required residual-voltage margin. |
| Typical medium-voltage system example | Three-phase 33 kV network with outdoor substation or line equipment. | A commonly evaluated starting point is an arrester with approximately 24.4 kV MCOV and 30 kV rated voltage, subject to system studies. | Use the network’s actual phase-to-earth voltage, temporary overvoltage profile, and insulation coordination results. | Verify neutral grounding, earth-fault clearing time, switching-surge severity, pollution classification, and transformer withstand level. |